1 min readUpdated 23 September, 2026

Daily (2–3 minutes total)

TaskTime
Check and record interior temperature1 min
Verify the door closes and seals properly30 s
Visual check for ice build-up on the evaporator30 s
Listen for unusual noises or vibration30 s
Confirm stored product is not blocking airflow1 min

Weekly (35–50 minutes)

TaskTime
Clean interior walls and floor15–30 min
Inspect door gasket for tears, cracks, or compression set5 min
Clean the door gasket (including inside the folds)5 min
Check the condensate drain for blockages5 min
Verify the defrost cycle is functioning5 min

Monthly (about 60 minutes)

TaskTime
Clean condenser coils15–30 min
Inspect evaporator coils10 min
Check and clean evaporator fan blades10 min
Inspect door hinges and hardware10 min
Verify thermostat / controller accuracy against a reference5 min
Inspect panel joints and cam-lock seals10 min

The monthly condenser interval assumes a clean indoor location — dirtier sites need it more often. See adjusting frequency and keeping records. For the cleaning methods behind these tasks, see cleaning procedures and condenser maintenance; for gasket renewal, see door gasket replacement.


This schedule applies to MTH Algor cold rooms with Daikin refrigeration supplied by Frostbox. Original MTH gaskets are available on request — contact [email protected].