Check the setpoint, independent readings and whether stock sits in the direct evaporator discharge.

In short: freezing in one location often means poor placement; freezing throughout may mean a sensor or control fault.

Do not calibrate by guesswork or alter service parameters. If cooling continues after the setpoint is reached, call a technician.

Symptoms

Temperature falls below setpoint, product freezes in a chiller, and ice forms on stock.

Causes and fixes

Possible causeHow to checkSolution
Thermostat set too lowRead the controller display or dial.Reset the setpoint to the correct value.
Faulty thermostat or sensorCompare the controller reading against an independent thermometer.Recalibrate or replace the sensor; call a technician if needed.
Product too close to evaporatorStock sitting directly in the cold-air discharge freezes first.Rearrange storage; keep a 100 mm minimum gap from the evaporator.
Stuck expansion valveEvaporator runs extremely cold with an unusual frost pattern.Requires a refrigeration technician — do not attempt to free it yourself.

Why a chiller freezes

Chilled rooms run only a few degrees above 0 °C, so a sensor reading low by even 2–3 °C, or product parked in the discharge stream, is enough to drop pockets below freezing. Always verify the controller against a second, independent thermometer before assuming the refrigeration is at fault.


If the controller and an independent thermometer disagree, contact [email protected] for service options.