Open doors admit warm, humid air. A simplified estimate uses Q = V × n × density × enthalpy difference / 86,400.

In short: the uncertain input is air changes; it depends on opening size, time, traffic, curtains and building pressure.

Use a recognised method for final design. Reduce load with short openings, good seals, closers and suitable barriers.

The formula

Q_infiltration = V × n × ρ × Δh / 86 400

  • V = internal volume (m³)
  • n = air changes per day (from the table below)
  • ρ = air density (~1.2 kg/m³)
  • Δh = enthalpy difference between outside and inside air (kJ/kg)
  • divide by 86 400 (seconds per day) to express the result in kilowatts (kW) — multiply by 1 000 for watts (Δh is in kJ/kg)

Air changes per day

Air changes per day fall as the room gets bigger (the open door is a smaller fraction of the volume) and rise with traffic:

Room volumeHeavy use (changes/day)Normal use (changes/day)
5 m³4417
10 m³3212
25 m³207.5
50 m³145.3
100 m³103.8

Reducing infiltration

Reducing infiltration is the cheapest load you can engineer out. Strip curtains, air curtains, fast-acting or self-closing doors, and disciplined door procedure all cut n directly. For freezers, this also reduces frost build-up on the evaporator.

See Door types and specifications for the hardware that lowers n.


For a checked calculation, use the Frostbox size calculator or contact [email protected].